Type USE-2 or RHW-2 or RHH Building Wires 2kV
DOWNLOADS | |
![]() |
TYPE RHW-2 SPEC. SHEET |
APPLICATIONS:
Where NEC jurisdiction applies; as Type RHW-2, 90 deg.C. in wet or dry locations, installed in air, conduit, or other recognized raceway. Sizes 1/0 and larger may be installed in cable tray per Article 318 of NEC. Otherwise, for general purpose applications at maximum conductor temperature of 90 deg.C. locations – including conduit, duct, tray trough, direct burial, and aerial installations.
CONSTRUCTION:
Stranded tinned or bare copper conductor, black XLP insulation, surface printed.
STANDARDS:
- Conductors conform to ASTM B-3 & B-8 (& B-33 for tinned copper conductor).
- RHW-2 Type ( 90 Deg.C. wet or dry) 2000 Volts per UL Standard 44.
- Cables designed to pass the IEEE-383 ribbon burner flame test and UL 1277.
- Jacket suitable for sunlight, oil & gasoline resistant applications I & II.
- Cables meet requirements of ICEA S-95-658/NEMA WC70.
BASIC CAT. NO. |
SIZE/AWG. KCMIL |
STRD. |
INSUL. mils |
O.D.in. |
AMPS 90° C |
WEIGHT lbs/m ft. |
---|---|---|---|---|---|---|
5-207-2K |
8 |
7 |
80 |
.320 |
45 |
77 |
5-208-2K |
6 |
7 |
80 |
.350 |
65 |
110 |
5-209-2K |
4 |
7 |
80 |
.400 |
85 |
165 |
5-210-2K |
2 |
7 |
80 |
.460 |
120 |
248 |
5-211-2K |
1 |
19 |
95 |
.530 |
140 |
318 |
5-212-2K |
1/0 |
19 |
95 |
.570 |
155 |
390 |
5-213-2K |
2/0 |
19 |
95 |
.610 |
185 |
480 |
5-214-2K |
3/0 |
19 |
95 |
.670 |
210 |
595 |
5-215-2K |
4/0 |
19 |
95 |
.720 |
235 |
738 |
5-216-2K |
250 |
37 |
110 |
.800 |
265 |
880 |
5-217-2K |
300 |
37 |
110 |
.850 |
295 |
1040 |
5-218-2K |
350 |
37 |
110 |
.900 |
325 |
1205 |
5-219-2K |
400 |
37 |
110 |
.950 |
345 |
1368 |
5-220-2K |
500 |
37 |
110 |
1.03 |
395 |
1688 |
5-221-2K |
600 |
61 |
125 |
1.14 |
455 |
2035 |
5-222-2K |
750 |
61 |
125 |
1.24 |
500 |
2515 |
5-223-2K |
1000 |
61 |
125 |
1.39 |
585 |
3315 |